The Sunsynk inverters are fully compatible with the Hubble Cloudlink and full range of batteries.
The following guide will assist with the correct battery settings you should use.
​
For further detailed information ensure you read the manual of the supplied battery regarding the setup and installation instructions.
sunsynk INVERTER SET UP
INVERTER examples

5KW

8KW

12KW
Model | Voltage | Bulk/Equalised (Vdc) | Float Voltage (Vdc) | Cutoff Voltage (Vdc) | Recommended Charge Amps | Max Discharge Current (A) |
---|---|---|---|---|---|---|
S Series | 12V
| 14
| 14 | 12 | 30A | 100A |
X-100 | 48V | 52.8 | 52.8 | 44 | 30A | 100A |
X-101 | 48V | 53.8 | 53.8 | 44 | 30A | 100A |
X-200 | 36V | 41.5 | 41.5 | 34 | 30A | 100A |
AM-2 | 48V | 53.8 | 53.8 | 44 | 30A | 100A |
AM-3 | 48V | 53.8 | 53.8 | 44 | 20A | 50A |
AM-4 | 24V | 29 | 29 | 23.8 | 30A | 100A |
AM-5 | 48V | 55.2 | 55.2 | 47 | 30A | 100A |
AM-10 | 48V | 55.2 | 55.2 | 47 | 60A | 150A |
BLADE | 48V | 55.2 | 55.2 | 47 | 50A | 200A |
The below settings are the recommended settings to use for the corresponding Hubble Lithium battery, as seen on the Sunsynk display. AC and normal lights should appear green. Shutdown settings under your discretion.



Note: These images are for display purposes only. Please refer to the above table for inverter settings.
If you are using a Hubble Cloudlink in your installation, it needs to be configured and wired up correctly if you want to monitor the inverter.
​
BRIEF OVERVIEW WITH SPECIFICS RELEVANT TO THE SUNSYNK
Wiring:
-
The battery serial cable will go between the Cloudlink’s “S” port (i.e. Serial port) and the battery’s serial port (RS232).
-
The BMS CAN cable will go between the Cloudlink’s CAN port and the SunSynk’s BMS_CAN port.
-
The RS485 cable will go between the Cloudlink’s MUL (Multi) port and the Sunsynk’s BMS_485 port.
Cloudlink Configuration:
Under the Cloudlink’s Device Settings set:
-
CAN SPEED to 500k
-
CAN MODE to Universal
-
CANN CONN. TO Inverter
-
RS485/MOD CONN. TO Inverter (Deye/SunSynk)
-
SERIAL CONN TO Battery
The quick setup guide describes how to access the device settings. Note the device settings can also be accessed on the CloudLink Portal, using the “Remote Console” feature, once the Cloudlink is online.
pin layout
cloudlink
​
PLEASE NOTE:
-
Connect straight RJ45 to RJ45 with only two wires - 1500mm.
-
Ensure that the clip is pointed away from you when counting the pins.
-
The Hubble Lithium BMS pinouts are the same as the Cloudlink CAN pinouts.
-
The AM-5 Batteries only use pins 4 and 5 to pins 4 and 5.

Pin | CLOUDLINK-MUL | INV - RS485 | CLOUDLINK CAN | INV - CAN |
---|---|---|---|---|
1 | N/A | N/A | N/A | N/A |
2 | N/A | N/A | GND | GND |
3 | N/A | N/A | N/A | N/A |
4 | N/A | N/A | CAN-H | CAN-H |
5 | N/A | N/A | CAN-L | CAN-L |
6 | N/A | N/A | N/A | N/A |
7 | RS485 A | RS485 A | N/A | N/A |
8 | RS485 B | RS485 B | N/A | N/A |
5KW & 8KW
​
PLEASE NOTE:
-
Below are the Hubble BMS, Cloudlink, and Sunsynk side pinouts.
-
Note that the Hubble Lithium BMS pinouts are the same as the Cloudlink CAN pinouts.
-
If you have the latest 5KW & 8KW with only 1 port (CAN/485) then use pins 4, 5 & 6
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​
​

HUBBLE DIP SWITCH SETTINGS FOR MULTIPLE BATTERY INSTALLATION
​
​For correct setup and communication each battery needs a unique serial address in order to communicate. If you are only using one battery in your setup, consider this the master battery and ensure you set it to address 1.
am-2

am-5 & AM-10

INVERTER SETTINGS
cloudlink setup
COMMON CLOUDLINK - DEYE SETUP QUERIES
​
-
The inverter RS485 address not configured.
Solution: Set the inverter to "slave" and configure address 1 to enable the port.
-
Inverters may have older firmware. It takes more than 2.5 sec to respond to RS485 commands, which then cause timeouts on the bus.
Solution: Ensure the firmware is up to date.
-
In some early firmware versions Deye/Cloudlink firmware, not all the data was available via Modbus. This has been rectified in the newer firmware versions.
-
On some inverter hardware versions if you use both CAN bus and RS485 at the same time and use 8 core straight CAT5 then RS485 pin A is short-circuited to GND and comms won’t work.
Solution: Only use the needed pins or wires on the CAT 5 cable, do not use a straight cable.
Required pins for CAN bus: 2, 4 and 5 only.
Required pins for RS485: 7 and 8 only - as illustrated above.
-
Older Cloudlink models need to be checked for hardware compatibility with Technical Support. Incompatible models need to be updated with Support directly.
​​
How do you setup multiple batteries?
See table above and check your product manual for a more detailed explanation. You will have to set dip switch settings per battery to give them a unique address. You also have to connect the included RJ45 battery link cables into the "Battery Link" port of each battery. Ensure your master battery dip switch 1 is on, 2,3,4 is OFF. Only the master battery CAN Bus will be enabled. You can then connect the Hubble Cloudlink into the CAN port of the master battery for communications to work.
​
​
Do I have to use the communication battery link cables if i dont want to monitor or have communications?
Yes
​
​